ITFAS-Level-1 Inspection and Testing of Fire Alarm Systems Level I Exam Questions and Answers

Questions 4

According to NFPA 72, which statement is true as it pertains to the testing of audible alarm notification appliances?

Options:

A.

Sound pressure levels are required to be taken during initial acceptance and periodic testing.

B.

Sound pressure levels are required to be taken during initial acceptance and reacceptance testing.

C.

Sound pressure levels are required to be taken in hallways only during initial acceptance testing.

D.

Sound pressure levels are required to be taken in sleeping areas only during initial acceptance testing.

Buy Now
Questions 5

The fire alarm control unit shows a supervisory signal on the display. What is the possible cause?

Options:

A.

A duct smoke detector is in alarm.

B.

A manual fire alarm box has been activated.

C.

A spot smoke detector is in alarm.

D.

A waterflow alarm has been activated.

Buy Now
Questions 6

According to NFPA 72, which date shall be marked on batteries?

Options:

A.

Month and year of expiration

B.

Month and year of inspection

C.

Month and year of installation

D.

Month and year of manufacture

Buy Now
Questions 7

How frequently should control equipment for a fire alarm system that is unmonitored for alarm, supervisory, and trouble signals be visually inspected?

Options:

A.

Daily

B.

Weekly

C.

Semiannually

D.

Annually

Buy Now
Questions 8

Secondary power shall automatically provide power to a protected premises system within how many seconds after the primary power fails?

Options:

A.

10

B.

30

C.

60

D.

90

Buy Now
Questions 9

What is the maximum extended interval allowed for equipment to get inspected?

Options:

A.

3 months

B.

6 months

C.

12 months

D.

18 months

Buy Now
Questions 10

After the secondary power supply has operated the fire alarm system under quiescent load,the secondary power shall be capable of operating all alarm notification appliances for which length of time?

Options:

A.

5 minutes

B.

10 minutes

C.

1 hour

D.

24 hours

Buy Now
Questions 11

In a Class B initiating circuit, wires should be monitored for integrity by having a supervisory device connected to which of the following?

Options:

A.

Anywhere on the loop

B.

Beginning of the loop

C.

The first detector

D.

The last detector

Buy Now
Questions 12

An inspector is testing the ground-fault monitoring circuit on the control panel. How does the inspector perform this test?

Options:

A.

Remove the primary power to the main control panel.

B.

Remove the signaling line circuit from the main control panel.

C.

Verify presence of a ground fault with a meter using the ohm scale.

D.

Verify the ground-fault indication when circuits are grounded.

Buy Now
Questions 13

A single open fault, in a Class A pathway, shall result in the annunciation of which of the following signals?

Options:

A.

Alarm

B.

Pre-alarm

C.

Supervisory

D.

Trouble

Buy Now
Questions 14

How often should radio transmitters be inspected?

Options:

A.

Monthly

B.

Quarterly

C.

Semiannually

D.

Annually

Buy Now
Questions 15

How should the documentation cabinet be labeled?

Options:

A.

Fire alarm documents

B.

Fire alarm record documents

C.

System records

D.

System record documents

Buy Now
Questions 16

Which three of the following branch circuit characteristics are required for circuit identification and accessibility of the fire alarm equipment's primary power supply? (Choose three.)

Options:

A.

The system circuit disconnect shall be permanently identified as "Fire Alarm."

B.

The system circuit disconnect shall be permanently identified at the control unit.

C.

Where a circuit breaker is the disconnecting means, a breaker locking device shall be installed.

D.

Where a circuit breaker is the disconnecting means, a breaker locking device shall be labeled.

Buy Now
Questions 17

Within a fire alarm control unit, what is the maximum delay in seconds for alarm system responses after the initiation device has been activated?

Options:

A.

10

B.

15

C.

30

D.

60

Buy Now
Questions 18

In the event of power loss, how long shall a secondary power source for household fire alarm systems maintain operation?

Options:

A.

24 hours in the normal condition followed by 4 minutes of alarm

B.

24 hours in the normal condition followed by 9 minutes of alarm

C.

24 hours in the normal condition followed by 10 minutes of alarm

D.

24 hours in the normal condition followed by 60 minutes of alarm

Buy Now
Questions 19

Which activity is required at the semiannual inspection of notification appliances?

Options:

A.

Verify candela setting

B.

Verify flash rate

C.

Verify location and condition

D.

Verify synchronization of strobes

Buy Now
Questions 20

Which two of the following should occur when a signal silence switch for a notification alarm is activated? (Choose two.)

Options:

A.

Audible appliances are deactivated.

B.

Door holders are deactivated.

C.

HVAC shutdown is deactivated.

D.

Visible appliances are deactivated.

Buy Now
Questions 21

How far away from the center line of the elevator door can a smoke detector be located?

Options:

A.

3 feet (1.0 meter)

B.

5 feet (1.5 meters)

C.

12 feet (3.7 meters)

D.

21 feet (6.4 meters)

Buy Now
Questions 22

Primary power supplies shall be functionally tested at which interval?

Options:

A.

Every month

B.

Every 3 months

C.

Every 6 months

D.

Every 12 months

Buy Now
Questions 23

What is the maximum travel distance between two fire alarm boxes measured horizontally on the same floor?

Options:

A.

30 feet (9.1 meters)

B.

60 feet (18.3 meters)

C.

90 feet (27 meters)

D.

200 feet (61 meters)

Buy Now